As an alternative to the time diagrams, the annual results for the selected building element can be displayed. The energy consumption by heating, cooling, appliances and lighting is summed up and also shown per floor area.

The maximum heating and cooling loads are the largest loads that occur in the building element, while the design heating/cooling loads refer to the time (month, day and time) when the heating or cooling load for the entire building is highest. Therefore the maximum loads are generally greater than the design loads.

The indicated latent part of the cooling load refers to the same point in time, so it is not the largest latent cooling load ever occurring. It should be noted that if the system capacity is limited, it is assumed that a central system is used, which can supply the rooms as required. The operating hours indicate how long the heating or cooling runs.
The energy balance indicates how the yearly heat inflow and outflow are made up.

For rooms, the over- and undertemperatures are displayed. They indicate the deviation of the perceived temperature from the setpoint band. The traffic time is the number of hours per year during which people are in the room.

The over/undertemperature hours indicate the number of hours in which the target value was exceeded or undercut by at least 0.5°C. The over/undertemperature degree hours are the yearly sum of the exact deviations. The frequency is calculated from the temperature hours and the traffic time, the average deviation from the temperature hours and the degree hours.

Zones, floors and the building have no temperatures of their own and therefore no over- and undertemperatures. Instead, the distribution of loads to the contained rooms is displayed. The desired load can be selected. Internal heat sources are people, equipment and lighting. For ventilation and transmission the sum of inflow and outflow is used.

The calculation results for the design days (when the heating or cooling load is highest) and the yearly results can be printed and saved. The maximum values of the rooms are shown there in the view "Room Peak Values" with the corresponding time. This function is available in the menu item "File" under "Print" and "Project report".