...
With the configuration module (via button "Change scheme") the desired system can be assembled quickly and easily. Via double click or the button "Select" the desired schema is taken over from the schema table into the representation of the system wiring.
In the case of a cascade connection, further heat pumps can be added or removed again after selecting the schema using an additional button. Next to the display, there is a slider on the right side of the screen which allows the display size to be changed with the mouse.
...
- Operating mode
- monovalent: Only the main heat generator is used to cover the heat demand.
- bivalent-alternative: The main heat generator covers the heating demand up to the set bivalence temperature. If the outside temperature drops below the bivalence temperature, the main heat generator switches off and the secondary generator is switched on.
- bivalent-parallel: The main heat generator covers the complete heating requirement up to the set bivalence temperature. If the outside temperature drops below the bivalence temperature, the secondary heat generator switches on and supports the main heat generator.
- Priority control - Determine here whether the heating or the domestic hot water should be heated first when there is a simultaneous demand for domestic hot water and heating.
- Heating limit temperature - If the outdoor temperature rises above the set heating limit temperature, the heating system is switched off completely.
- Cooling limit temperature - If the outside temperature falls below the set cooling limit temperature, the cooling function of the system (if present) is switched off completely.
- Optimize flow temperature ("Weather-compensated control") - Instead of the static flow temperature (of e.g. 35 °C), the flow temperature is adjusted so that the heat requirement of the room with the greatest heat demand is covered.
- Self-powered - If a PV system has been created in the project or if a CHP is used, you can use the generated electricity to operate the heat pump.
Control of individual system components
...