In the cooling profile, the operating times, the setpoint curve and the convective part of the cooling system are defined. The cooling system can be activated or deactivated by setting the corresponding status for the individual hours.
If the cooling system is deactivated, there is no cooling. The cooling load/cooling capacity during these hours is set to zero. This operation is interesting to analyze what happens if the zone is not air-conditioned. Some zones, e.g. staircases, are generally not air-conditioned. The supplied load consists of a convective and a radiant part (in %, both parts equal 100%). For the cooling system, the convective portion must be specified; if this is unknown, 50% must be entered here. The setpoint is defined hourly. This way you can generate any desired setpoint daily course. In order to maintain the setpoint, the cooling must also be active at this time. The setpoint value for cooling must not collide with the setpoint value for heating. If the heating setpoint is greater than the cooling setpoint, it is set to the cooling setpoint.