The presentation of the results is divided into four areas:
- Temperature profile [°C]
- Humidity [%]
- Heating and cooling load [kW]
- Thermal loads [kW]
The individual loads can be shown or hidden using check boxes. Some lines are only available for individual rooms, not when floors, zones or the entire building are selected, as these are only useful for individual rooms (e.g. the temperature of the indoor air).
A negative load means cooling, a positive warming.
The perceived temperature is the mean value of the air temperature and the mean surface temperatures of the building components.
When calculating the air humidity, the latent cooling must be applied in addition to the condensation at the cold output. It should be noted that it is not a thermal load. Therefore, of the total cooling load, only the sensitive part acts on the temperatures.
The loads caused by persons, equipment and lighting are determined by corresponding usage profiles.
When evaluating the lighting load, the connection with the lighting and sun protection control must be taken into account
The ventilation heat is calculated from the air volume and the difference between the outside and inside air temperature.
The components take up the sum of the loads (heat capacity of the air is only considered for the air exchange). It should be noted that the heat storage capacity of the walls is taken into account in the calculation procedure and that loads are absorbed by the walls and, if necessary, some of them are transferred to the outside. It is therefore not directly about the heat conduction through the building components.
For the selected building element, time diagrams, annual results or - if the humidity calculation is activated in the project options - also the comfort level are displayed on the right side, depending on the selection.